- Box volume. Use Table 314.16(A) for standard metal sizes, or the cubic inches stamped on the box.
- Outside conductors. Each conductor that enters from outside and terminates or splices counts one volume at its AWG. A transit without a splice counts one. A loop meeting the free-length rule counts two. Pigtails count zero.
- Clamps. All internal cable clamps together count one volume at the largest conductor in the box.
- Support fittings. Fixture studs and hickeys: one volume each kind, at the largest conductor in the box.
- Device yokes. Each yoke counts two volumes at the largest conductor connected to that device.
- Equipment grounding conductors. Group per the selected edition (see the EGC boost for 2020+ quarters).
- Compare. Required cubic inches versus box volume. Spare must be non-negative to pass in the app.
Table 314.16(B) volumes used in the app (in³)
| AWG | in³ |
|---|---|
| 18 | 1.5 |
| 16 | 1.75 |
| 14 | 2.0 |
| 12 | 2.25 |
| 10 | 2.5 |
| 8 | 3.0 |
| 6 | 5.0 |
Same conductor volumes appear across the 2017 / 2020 / 2023 editions in the app tables. Grounding allowances differ by edition.
Calculates box fill per the selected NEC edition. Local amendments may differ. Verify with your AHJ or inspector.