Calculate box fill in a repeatable order

Use the same order every time so you do not double-count clamps or miss a device yoke.

Conductor, device, and ground volume blocks for 314.16 counting
  1. Box volume. Use Table 314.16(A) for standard metal sizes, or the cubic inches stamped on the box.
  2. Outside conductors. Each conductor that enters from outside and terminates or splices counts one volume at its AWG. A transit without a splice counts one. A loop meeting the free-length rule counts two. Pigtails count zero.
  3. Clamps. All internal cable clamps together count one volume at the largest conductor in the box.
  4. Support fittings. Fixture studs and hickeys: one volume each kind, at the largest conductor in the box.
  5. Device yokes. Each yoke counts two volumes at the largest conductor connected to that device.
  6. Equipment grounding conductors. Group per the selected edition (see the EGC boost for 2020+ quarters).
  7. Compare. Required cubic inches versus box volume. Spare must be non-negative to pass in the app.

Table 314.16(B) volumes used in the app (in³)

AWGin³
181.5
161.75
142.0
122.25
102.5
83.0
65.0

Same conductor volumes appear across the 2017 / 2020 / 2023 editions in the app tables. Grounding allowances differ by edition.

Calculates box fill per the selected NEC edition. Local amendments may differ. Verify with your AHJ or inspector.

Next: know pass or fail before you close the wall.