- Sum required cubic inches for conductors, clamps, fittings, devices, and grounds.
- Confirm box volume from Table 314.16(A) or the stamp.
- Compute spare (box minus required). Negative spare means fail.
- If it fails, upsize the box or add a listed ring before trim-out.
- Record the edition you used.
Calculates box fill per the selected NEC edition. Local amendments may differ. Verify with your AHJ or inspector.