Most fill mistakes come from treating a device as one volume, counting every clamp, or mishandling grounds.

Device yoke and grounding volume blocks

Device yokes

A device on one yoke counts as two conductor volumes based on the largest conductor connected to that device. A GFCI receptacle is still two volumes, not “extra because GFCI.” Wider devices that occupy more than one gang take two volumes per gang occupied under the rules implemented here.

Clamps

One or more internal cable clamps share a single volume allowance at the largest conductor in the box. Do not multiply by the number of clamps.

Support fittings

Fixture studs and hickeys each add one volume (per kind) at the largest conductor in the box.

Equipment grounding conductors

EGCs are grouped. Under NEC 2020 and 2023 as implemented in the app, up to four EGCs share one volume; each additional EGC adds one quarter of the largest EGC. Confirm the edition on site. Details: EGC quarter allowance.