- Up to four equipment grounding conductors share one volume based on the largest EGC.
- Each additional EGC adds one quarter of that largest EGC volume.
- 2017 grouping differs; pick the edition that matches the job.
Deeper context: device yokes, clamps, and grounds.
Calculates box fill per the selected NEC edition. Local amendments may differ. Verify with your AHJ or inspector.